Post Offer Free
Wuhan Huaying Electric Power Tech & Science Co.,ltd
Wuhan Huaying Electric Power Tech & Science Co.,ltd  

Gold Index: 4924

You are here: home  > All Test Equipment  > CT Tester HYVA 405

CT Tester HYVA 405 

Price: 1.0~2.0 USD 
Payment Terms: T/T,L/C,D/A,D/P,WU 
Place of Origin: Hubei, China (Mainland) 
inquire skype
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: HYVA-405
Production Capacity: 100 sets
Delivery Date: 7 working days
Means of Transport: Ocean,Air
Packing: wooden case

made in china wuhan city, huaying electric power.

Introduction


Model HYVA-405


Tests for Current Transformer:

1 Excitation curve and parameters test 
2 Turns ratio test 
3 Ratio and phase error test 
4 Polarity mark check 
5 Winding resistance measurement 
6 Secondary loop burden measurement 
7 Error line curve test for protection CT 
8 Transient CT parameters test 
9 CT nameplate guess 
10 Saturation hysteresis loop curve measurement

Tests for Voltage Transformer:

1 Turns ratio test 
2 Ratio error and phase angle error test 
3 Polarity test 
4 Secondary burden test 
5 Winding resistance test


Application


CT PT Tester application 
1 CT nameplate check 
2 CT parameters check in work burden 
3 CT transient parameters analysis 
4 CT ratio and phase error calibration 
5 PT routine test


Technical index


1 Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13 
2 Power supply: AC220V±10%, 50/60Hz±10% 
3 Voltage output: 0.1~180V (AC) 
4 Current output: 0.001~5A(RMS) 
5 Power output: 500VA 
6 Maximum knee voltage measurement: 45KV 
7 Current measurement: 
  Range: 0~10A (automatically change range in 0.1/0.4/2/10A)  
  Error: <±0.1%+0.01%FS 
8 Voltage measurement: 
  Range: 0~200V (automatically change range in 1V/10V/70V/200V) 
  Error: < ±0.1%+0.01%FS 
9 Turns ratio measurement: 
  Range:1~35000 
  1~2000     error<0.05% 
  2000~5000  error<0.1% 
  5000~35000  error<0.2% 
10 Phase measurement: error: ±2min; resolution: 0.01min 
11 Winding resistance measurement:  
   Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm) 
   Error: < 0.2%RDG+0.02%FS 
   Maximum resolution: 0.1mΩ 
12 Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree 
13 CT Secondary burden: 
   Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm) 
   Error: <0.2%RDG+0.02%FS  
   Maximum resolution: 0.001ohm 
14 PT Secondary burden: 
   Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm) 
   Error :<0.2%RDG+0.02%FS  
   Maximum resolution: 0.1ohm 
15 PT ratio measurement: 
   Range: 1~35000 
   1~10000 error<0.1% 
   10000~35000 error<0.2% 
16 PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1% 
17 PT phase angle measurement: maximum error < 3min 
18 Make evaluation for test results according to selected standards 
19 Make word report for test result 
20 Make word reports one time for multi-group test records on the PC 
21 Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test 
22 Compare excitation curves with saved excitation curves in the same window 
23 Memory capacity: >1000 groups test results  
24 Working condition: temperature: -10℃~50℃; moist: ≤90% 
25 Size: 485mm×356mm×183mm 
26 Weight: <15kg


Contact information


 Email whhy818@163.com Name Chloe shuyue wang. Skype Wangshuyue1991


Ms. Chloe Shuyue Wang
skype Ms. Chloe Shuyue Wang
sales manager
Tel: 86-27-82850969
Mobile: 158 2728 0740
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Related Products

Company Info

Wuhan Huaying Electric Power Tech & Science Co.,ltd [China (Mainland)]


Business Type:Manufacturer, Trading Company, Distributor/Wholesaler
City: Wuhan
Province/State: Hubei
Country/Region: China (Mainland)

wuhan huaying:   skype
wuhan huaying:   qq

You May Like: